2 compact (8200), Compact (8200), Error messages – Lenze Engineer v2.21 User Manual
Page 252

Error messages
Communication entity generator
252
Lenze · Engineer · 2.13 EN - 10/2014
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.4.2
Compact (8200)
Unexpected error [CECOMP0001]
Different transfer modes for CAN1 IN/OUT [CECOMP0002]
COB-ID {0} has been assigned several times for nodes [CECOMP0003]
Baud rate of {0}k is not supported by node [CECOMP0004]
Error during writing on object [CECOMP0005]
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
The transfer modes have been coupled for the CAN1
objects of the controller.
CAN1-IN and CAN1-OUT have to be transferred in a
synchronised manner or asynchronously.
The following combinations are permissible:
CAN1-IN
CAN1-OUT
Synchronous
Synchronous
Asynchronous
Time or event
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
Assigning the same COB-ID several times for fixed
process data objects is not allowed for a 9300.
Ensure that no ports of a 9300 device are connected to
each other in the function block editor.
By this, the ports would receive the same COB-IDs.
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
The baud rate cannot be transferred to the associated
code.
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
Object could not be written.