4 communication entity generator, 1 standard (9300 servo + 9300 servoplc), Communication entity generator – Lenze Engineer v2.21 User Manual
Page 249: Error messages

Lenze · Engineer · 2.13 EN - 10/2014
249
Error messages
Communication entity generator
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.4
Communication entity generator
Standard (9300 servo + 9300 ServoPLC)
I/O system IP20 (modular and compact)
12.4.1
Standard (9300 servo + 9300 ServoPLC)
Unexpected error [CESTD0001]
Baud rate of {0}k is not supported by the nodes [CESTD0002]
COB-ID {0} is assigned to several nodes [CESTD0003]
Error during writing on object [CESTD0004]
Error during writing of parameter value {0} [CESTD0005]
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
The baud rate cannot be transferred to the associated
code.
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
It is not permissible for a 9300 to assign the same COB-ID
several times to fixed process data objects.
Ensure that no ports of a 9300 device are connected to
each other in the function block editor. By this, the ports
receive the same COB-IDs.
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
Object could not be written.
Response (Lenze setting printed in bold)
Error Warning Information
Cause
Remedy
Parameter value could not be written to the code.