beautypg.com

Modifying the target address timeout – Allied Telesis AT-S70 User Manual

Page 211

background image

AT-S70 Management Software User’s Guide

211

This is the name of the SNMP manager, or host, that manages the
SNMP activity on your switch. You can enter a name of up to 32
alphanumeric characters.

The following prompt is displayed:

Enter UDP Port#: [0 to 65535]-> 162

7. Enter a UDP port.

You can enter a UDP port in the range of 0 to 65,535. The default UDP
port is 162.

8. From the Main Menu, select System Configuration.

The System Configuration Menu is displayed, as shown in Figure 10
on page 46.

9. From the System Configuration Menu, select Save Configuration

File.

Modifying the Target Address Timeout

The Target Address Timeout parameter only applies when the message
type is an Inform message. To modify the Target Address Timeout
parameter in an SNMPv3 Target Address Table entry, perform the
following procedure.

1. From the Main Menu, select System Configuration.

The System Configuration Menu is displayed, as shown in Figure 10
on page 46.

2. From the System Configuration menu, select SNMPv3

Configurations.

The SNMPv3 Configurations menu is displayed, as shown in Figure 61
on page 147.

3. From the Configure SNMPv3 User Table menu, select Configure

SNMPv3 Target Address Table.

The Configure SNMPv3 Target Address Table menu is displayed, as
shown in Figure 77 on page 205.

4. From the Configure SNMPv3 Target Address Table menu, select

Modify SNMPv3 Table Entry.

The Modify SNMPv3 Target Address Table menu is displayed, as
shown in Figure 78 on page 209.