Publication 1757-IN040B-EN-P - March 2002

ProcessLogix Server Upgrade Procedures 4-9

2. Logon to SERVERB as ps_user.

Synchronizing Server Databases on Redundant Servers

The following can be performed on the Primary or Backup Server.

1. Click Start

Programs

ProcessLogix Server

Station.

2. Click View

System Status

Server Redundancy to call up the

Server redundancy display.

3. Click the Oper field in the lower right corner of the display.

4. Key in >mngr< in the Station Logon prompt and click OK.

5. Click Synchronize. When the Synchronize Databases (Y/N)

prompt appears, key in >Y< in the entry field above the display
and press .

6. Wait for the synchronization to complete (“Synchronization

Complete” prompt appears) and verify that the display shows
simulated Green LED indications for the following states:

Primary Server

Running

Backup Server

Synchronized

Running

Link Status

Link 0 (LNK00) - Active link

7. Click Station

Exit.

8. Click Yes to exit Station.

IMPORTANT

All R400.0 Systems are required to use the ps_user
account. This is a change from R320.0, where most
systems used the plx_user account.