User interface capacity and performance, User interface capacity and performance -9 – Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual
Page 261
![background image](/manuals/579140/261/background.png)
Publication 1757-IN040B-EN-P - March 2002
Performance and Capacity Specifications 11-9
User Interface Capacity and
Performance
Table 11.E Operational Display Update Rates
Operation Display Update Rates
Maximum Continuous Display Update Rate
1 sec
Typical Field Change to Display Update Time with 100 Parameters
Per Display on a Single Station/Server
(Server configured for 1 sec update)
< 2 sec
Typical Display Call Up Time with 100 Parameters on a Single
Station/Server
(Call up time is dependent on display complexity; this excludes
the first initial call up.)
< 2 sec
Maximum Number of Stations Connected to one Server
20
Maximum Number of Concurrent Users Connected to one Server.
See Table 11.K Server communication NetBIOS session capacity
on page 11-18.
Unlimited for Windows 2000
Sever based system
Table 11.F Multi-user CB/FLM Operational Limits
Multi-user CB/FLM Limits
Maximum CB Clients connected to single Server
4
Remote Access Service (RAS) support for Multi-User CB
Not Supported
Dial-up Networking support for Multi-User CB
Not Supported
Minimum continuously available Network Bandwidth required for each
multi-user CB Client.
128KB
Maximum Fieldbus Library Manager Clients connected to a single server
1