Publication 1757-IN040B-EN-P - March 2002

11-20 Performance and Capacity Specifications

I/O Specifications

Table 11.N I/O Module Capacity

The following applies to the Phase 2 Fieldbus integration using the 1757-FIM with controlled support
for Phase 1 Fieldbus interface using the CN2FF.

I/O Module and Fieldbus Capacity

50 ms CEE

5 ms CEE

Maximum Number of IOMs per 1757-PLX52
(1756/1757 + 1797 FLEX Ex + 1794-FLEX I/O + CN2FFs + 3*1757-FIMs 2*SST-PFBCLX’s+
4*TC-MUX021 FTA’s + in any combination.

64

12
(local 1757/1756
I/O only)

Maximum Number of Remote I/O Chassis + 1757-FIM-Only Chassis+Remote Mixed
Chassis, 1794/1797-ACNR15s (combined) per 1757-PLX52.

8

0
(local 1757/1756
I/O only)

Maximum Number of IOMs per Downlink 1756-CNB
(1756/1757 + 1797 FLEX Ex + 1794 FLEX I/O + CN2FFs + 3*1757-FIM’s + 6* SST-PFBCLX’s +
4*TC-MUX021 FTA’s + 1.5*1757-PIM’s in any combination.

64 scheduled

24
unscheduled

0
(local 1757/1756
I/O only)

Maximum number of Downlink 1756-CNB’s per Controller Chassis

4

0
(local I/O only)

Serial Interface Module: (TC-MUX021) related only

Maximum Number of Serial Interface Modules per 1757-PLX52

3

1

Maximum Number of FTA assemblies per Serial Interface Module (TC-MUX021)

Each FTA connected counts as 4 IOMs in the 64 Max IOM/1757-PLX52 and the 24
IOMs/1756-CNB calculation above.

2

2

1788-CN2FF related only:

Maximum number CN2FFs per 1757-PLX52

Each Linking Device counts as 1 IOM in the 64 IOM/1757-PLX52 calculation above.

8

Not Supported

Maximum number CN2FFs per Non-Redundant Server

8

Not Supported

Maximum number CN2FFs per Redundant Server (NI-FBUS Service and NI Configurator
must be run on the Backup Server only)

48

Not Supported

Maximum number CN2FFs per NI Configurator Project

1

0

Maximum Number of H1 segments per CN2FF

2

Not Supported

Maximum number of CN2FF Devices per H1 segment connected to a CN2FF.

10

Not Supported

1757-FIM Related Only

50ms CEE

5ms CEE

Maximum number 1757-FIM’s per 1757-PLX52

Each 1757-FIM counts as 3 IOMs in the 64 IOMs/1757-PLX52 calculations above.

21

Not supported

Maximum number 1757-FIMs per Server (Redundant or Non-Redundant)

100

Not Supported

Maximum number of H1 segments per 1757-FIM

2

Not supported

Maximum number of FF Devices per H1 segments connected to a 1757-FIM.
(other constraints may be encountered before this constraint)

16

Not Supported