Additional Redundant Server Procedures 6-7
b. Click Yes to confirm the action and wait for the Server to
change its state.
c. Close the ProcessLogix Server dialog box.
3. Are you using a dual network (LAN) data link with your
redundant Servers?
•
If the answer is Yes, go to Step 4.
•
If the answer is No, go to Step 9.
4. Use Windows NT Explorer to locate the redun.hdw file in this
directory path:
C:\Honeywell\server\user
5. Double-click the redun.hdw file to open it in Notepad. Modify
the file to include the following entries for dual data links.
This is only required if you have redundant LANs.
DEL LNK00
ADD LNK00 NETWORK_LINK
DEL LNK01
ADD LNK01 NETWORK_LINK
The default file definition is for a single network (LAN) data link.
6. Click File
⇒
Save to save your changes to the file.
7. Close Notepad.
8. Click File
⇒
Close to exit Explorer.
9. Click Start
⇒
Run.
10. Key in this command in the Open entry field:
>cmd<
and click OK to open the DOS window.
IMPORTANT
For information about the required operator actions
for the setup of fast failover, navigate in Knowledge
Builder to Server and Client Configuration
Guide
⇒
Configuring and Monitoring Redundant
Server System
⇒
Server Redundancy Fast Failover
Configuration topic for HOSTS file and redundant
hardware build details.