Additional Redundant Server Procedures 6-7

b. Click Yes to confirm the action and wait for the Server to

change its state.

c. Close the ProcessLogix Server dialog box.

3. Are you using a dual network (LAN) data link with your

redundant Servers?

If the answer is Yes, go to Step 4.

If the answer is No, go to Step 9.

4. Use Windows NT Explorer to locate the redun.hdw file in this

directory path:

C:\Honeywell\server\user

5. Double-click the redun.hdw file to open it in Notepad. Modify

the file to include the following entries for dual data links.

This is only required if you have redundant LANs.

DEL LNK00
ADD LNK00 NETWORK_LINK
DEL LNK01
ADD LNK01 NETWORK_LINK

The default file definition is for a single network (LAN) data link.

6. Click File

Save to save your changes to the file.

7. Close Notepad.

8. Click File

Close to exit Explorer.

9. Click Start

Run.

10. Key in this command in the Open entry field:

>cmd<

and click OK to open the DOS window.

IMPORTANT

For information about the required operator actions
for the setup of fast failover, navigate in Knowledge
Builder to Server and Client Configuration
Guide

Configuring and Monitoring Redundant

Server System

Server Redundancy Fast Failover

Configuration topic for HOSTS file and redundant
hardware build details.