4-10 ProcessLogix Server Upgrade Procedures

Importing the ProcessLogix Server Points Database

1. Logon to the system as ps_user.

2. Click Start

Run.

3. Key in this command in the Open entry field:

>cmd<

and click OK to open the DOS window.

4. At the DOS prompt, key in the following command:

>hscserver /stop /y<

and press Enter.

5. After Completed successfully, key in the following command:

>hscserver /unload /y<

and press Enter.

6. To copy the points database, key in the following command:

>Copy C:\Honeywell\server\data.upgrade\points C:\Honeywell\server\data<

7. Press Enter.

8. To start the ProcessLogix Database, key in the following

command:

hscserver /load /y

and press Enter.

9. To import the data, key in the following command:

>sysbld -restore C:\Honeywell\server\data.upgrade\data -default -y<

ATTENTION

!

For Redundant systems, these steps are performed
on the SERVERA node, with the SERVERB node