Operating System Installation Procedures 2-15
•
Confirm the password.
•
Click Next.
13. At the Date and Time Settings window:
•
If necessary, adjust the Date and Time settings.
•
Set the appropriate Time Zone for your location.
•
Uncheck the Automatically adjust clock for daylight saving
changes option.
•
Click Next.
14. If setup has not found a suitable Network Device, you will be
prompted for installing one. Follow the instructions for adding a
manufacturer supplied driver or add the Microsoft Loop Back
adapter.
15. Choose the Custom settings option and click Next.
16. At the Networking Components window, select Internet Protocol
(TCP/IP) and click Properties.
17. Choose the Use the following IP Address option.
•
Fill in the appropriate IP address.
IMPORTANT
Be sure to document the Administrator Password. (It
is required later in the procedure.) The Administrator
Account and password gives a user full access to the
system. Care should be taken to who has access to
this information.
ATTENTION
!
Failure to uncheck the Automatic adjustment for
Daylight Savings Time will cause Redundant
Systems to loose “Sync” when the time is
automatically adjusted. Choosing not to
automatically adjust the time allows you to decide
when to make the adjustment (at a time that is not
critical to your process).
ATTENTION
!
IP Addresses are critical to the communication of
the system. Rockwell Automation suggests, when
possible, to utilize a Private Network for the control
system. (Not connected to any other networks.)
This isolates the control system from interference
from any business communication.