14. Select the contents (CMs, SCMs, IOMs) of the CEE folder and

click Edit

Delete.

15. Click Delete Selected object(s) to delete the selected objects.

16. Click the CPM icon, and click Edit

Delete.

17. Click Delete Selected object(s) to delete the non-redundant

CPM.

18. In Project tab, click the CEE folder icon.

19. Click Tools

Assign to call up the Controller Assignments dialog

box.

Confirm that the check boxes for the selection Show CMs and
Show IOMs are checked.

20. Select the CEE associated with the non-redundant CPM in the

Select a CEE list box.

21. Select all the modules listed in the Assigned Modules list box.

Document the modules you will be unassigning.

22. Click Unassign.

Wait for modules to be unassigned and removed from the
Assigned Modules list box.

23. Click Close and return to the Project tab.

24. Click the CPM icon and click Edit

Delete.

25. Click the Delete Selected object(s) button to delete the CPM and

its associated CEE.

26. Close Control Builder.

Installing and connecting Redundant Chassis Pair (RCP)
Hardware

Refer to the following data in Knowledge Builder for general
information about Controller redundancy and how to install and
connect the 1757-PLX52, 1757-SRM Redundancy Module (SRM), and
1756-CNBR redundant ControlNet Bridge module (CNB).