Publication 1757-IN040B-EN-P - March 2002
ProcessLogix Server Installation Procedures 3-15
10. Restart the PC.
Updating the 1784-PCIC Firmware
Starting Network Tools Application
If this is the first time you have used Network Tools on this PC, refer
to Making First Time Network Tools Settings on page 8-9 and then
continue with this procedure beginning at Step 6.
1. Click Start
⇒
Run.
2. Key in this command in the Open entry field:
>ntools -c -u<
3. Click OK to launch the Network Tools application.
4. Click OK to acknowledge the warning about monitoring through
Control Builder.
5. Click Resume
to initiate network scan.
Updating the 1784-PCIC Firmware
6. Click the desired PCIC icon under the Desktop tree and wait for
the chassis to appear in the Detail pane.
7. Check the firmware revision.
•
If the Firmware is 3.5.33
– For redundant Server pair, skip to Completing the
ProcessLogix R400.0 Install on a Redundant Server Pair on
page 3-19.
IMPORTANT
Whenever the 1784-PCIC driver has been updated or
the Network Address is changed, the 1784-PCIC
driver must be stopped and restarted to complete the
change. You must power down the PC.
TIP
If the RSLinx and PCIC driver services for system
communications in ControlNet mode are not
running, this command will start the services.