Saving important data, Saving important data -17 – Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual
Page 191

Publication 1757-IN040B-EN-P - March 2002
Supplementary Procedures 8-17
Saving Important Data
For a redundant server pair, complete this on SERVERB only.
To export the Engineering Repository Database, do the following:
1. Logon to the Server as ps_user.
2. Create a sub-directory at the root of C,
ie. C:\ExportDB
3. Click Start
⇒
Programs
⇒
ProcessLogix Engineering Tools
⇒
Control Builder.
4. In the Login dialog box, make these entries:
a. Key in >mngr< as the default User Name.
b. Key in >mngr1< as the default Password.
c. Key in the name of the appropriate Server node in the Server
Name field.
5. Click OK.
6. Click File
⇒
Export.
7. Click Browse and select the directory created in step 2.
i.e. C:\EXPORTDB
8. Click Select All.
Depending on the size of your database, this may take several
minutes.
9. Click Export.
Depending on the size of your database, this step may take
several minutes to several hours.
ATTENTION
!
Process systems must export their Engineering
Repository Database at this time before proceeding.
The data that is saved during this step can be stored
on the existing system, but can NOT be contained
within the C:\Honeywell path.
For Example, create a sub-directory at the root of C:
ie C:\ExportDB.
If the system is brand new (ie, no configuration
applied yet.), then this procedure can be skipped.