beautypg.com

Synchronizing server databases on redundant server, Confirming databases are synchronized – Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual

Page 147

background image

Publication 1757-IN040B-EN-P - March 2002

Additional Redundant Server Procedures 6-13

Synchronizing Server Databases on Redundant Server

1. On SERVERA, click Start

Programs

ProcessLogix

Server

Station.

2. Click View

System Status

Server Redundancy to call up the

Server redundancy display.

3. Click the Oper field in the lower right corner of the display.

4. Key in >mngr< in the Station Logon dialog box and press

.

5. Click Synchronize. When the Synchronize Databases (Y/N)

prompt appears, key in >Y< in the entry field above the display
and press .

6. Wait for the synchronization to complete (“Synchronization

Complete” prompt appears) and verify that the display shows
simulated Green LED indications for the following states:

Primary Server

Running

Backup Server

Synchronized

Running

Link Status

Link 0 (LNK00) - OK Active link

Link 1 (LNK01) - OK Active link (Only applies if you are

using a dual LAN)

7. Click Station

Exit.

8. Click Yes to exit Station.

9. Verify redundancy has been established on both SERVERA and

SERVERB by using for DOS command C:\dual_status.

Confirming Databases are Synchronized

1. On SERVERA, click

Start