beautypg.com

Firmware revision level reference, Firmware revision level reference -5 – Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual

Page 163

background image

Publication 1757-IN040B-EN-P - March 2002

Firmware Maintenance Procedures 7-5

Firmware Revision Level Reference

The following table lists the firmware revision levels for listed
components that are current for R400.0 along with the directory
locations for firmware upgrade files.

ATTENTION

!

This release of ProcessLogix supports only the
firmware versions listed in Table 7.A. When installing
new systems or repairing existing systems, you must
ensure that all modules meet the firmware version
requirements listed in Table 7.A.

Table 7.A Hardware component firmware revision level reference for R400.0

Component
Name

Model Number

Revision
Level for
R400.0

Directory

File

Process Controller
Module

1757-PLX52
(redundant-
compliant)

PS400.0-19.1

C:\Honeywell\tps50\system\bin

Cee5.pcm
Cee50.pcm
Cpmboot.pcm

Serial Interface
Module (SIM)

TC-MUX021

PS400.0-19.1

C:\Honeywell\tps50\system\bin

Simboot.pcm
simrex.pcm

Use this base directory path to locate the firmware directories and files for the following modules:

C:\Honeywell\tps50\system\firmware

ControlNet Bridge
module (CNB)

1756-CNB/B
(single media)
1756-CNBR/B
(dual media)

2.27

cnb\1756-CNB(R)-B\2_27

99422005.nvs

1756-CNB/C
(single media)
1756-CNBR/C
(dual media)

4.24

cnb\1756-CNB(R)-C\4_24

99404317.nvs

1756-CNB/D
(single media)
1756-CNBR/D
(dual media)

5.25

cnb\1756-CNB(R)-D\5_25

99415512.nvs

Redundancy
Module (RM)

1757-SRM

2.11

\1757-SRM\2_11

rm.nvs

FLEX Ex ControlNet
Adapter

1797-ACNR15
(redundant media)

3.5

\1797-ACN(R)15\3_5

99423302.nvs

FLEX IO ControlNet
Adapter

1794-ACN15/C
(single media)
1794-ACNR15/C
(redundant media)

3.5

\1797-ACN(R)15\3_5

99423302.nvs