Controller redundancy, Controller redundancy -19 – Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual

Page 271

background image

Publication 1757-IN040B-EN-P - March 2002

Performance and Capacity Specifications 11-19

Controller Redundancy

ATTENTION

!

The Ethernet Module cannot be used with Controller
Redundancy

Table 11.M Controller Redundancy (50 ms CEE only) Specifications

Controller Redundancy (50 ms CEE only)

Redundancy compliant devices

CNB

1757-PLX52
1757-SRM
1757-BEM

Non-redundancy compliant devices (cannot be introduced in a
redundant controller chassis)

1756 IOM
TC-MUX021
1757-PIM
1757-FIM
SST-PFBCLX

Controller models supported

1757-PLX52 only

Control Processing Switchover Interruption Time

500 ms

Redundancy Module Cable Medium

Fiber Optic Cable

Redundancy Module Cable Lengths

1, 3, 10 meters

Redundancy Module Slot Width

2 slots

Initial Synchronization Timer (from Sync Start to Completion)

90 sec

Maximum Elapsed Time Between Commanded Switchover and
Completion of Initial Synchronization

120 sec

Maximum Elapsed Time Between Switchover Due to Power
Cycle of the Primary and Completion of Initial Synchronization

150 sec