10-12 New Functions and Features

%Cxx where xx is the percentage of CPU usage (range of 00 –
99).

KpOv indicates that the keeper is powering up or off line with
valid keeper information that may or may not match the
network keeper.

KpOi indicates that the keeper is powering up or off line with
invalid keeper information.

KpAv indicates that the keeper is the active network keeper,
with valid keeper information, whose keeper signature defines
the network keeper signature.

KpIv indicates that the keeper is an inactive network keeper with
valid keeper information that matches the network keeper
signature.

KpAi indicates that the keeper is the active network keeper
either with invalid keeper information or with a keeper
signature that does not match the network keeper signature.

KpIi indicates that the keeper is an inactive network keeper
either with invalid keeper information or with a keeper
signature that does not match the network keeper signature.

nCxx where xx is the number of open connections used by the
CNB (range of 00 – 20).

nUxx where xx is the number of unconnected buffers used by
the CNB (range of 00 - 20).

Bxnn where nn is the number of bandwidth-exceeded
occurrences since the last power cycle or module reset (range 00
– 99). The display rolls over beyond 100. Bandwidth exceeded
display is disabled until the first bandwidth exceeded event is
detected (all receive buffers in use and additional buffer is
needed – module clears all received buffers in an effort to
recover from resource overload).

Server

Updated Station

Station now supports the navigation to and the display of HTML pages
created with the ProcessLogix HMIWeb Display Builder.

Along with support for HMIWeb displays, the new version of Station
also fully supports all displays created with the existing ProcessLogix