beautypg.com

Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual

Page 170

background image

Publication 1757-IN040B-EN-P - March 2002

7-12 Firmware Maintenance Procedures

6. To load the personality image to a 1757-FIM, locate the

Fimrex.nvs personality (rex) file. See Table 7.A on page 7-5.

This example illustrates loading the personality image to a
1757-PLX52 for CEE-50ms.

7. When the correct file appears in the list box, select it so that it

appears in the File Name entry field.

8. Click Open to start the firmware load and click Yes to confirm

the action.

9. Wait for the load to complete and the 1757-PLX52, TC-MUX021,

or 1757-FIM module to reboot to its NODB status as shown in
the module LED display. The Status field in the lower portion of
the Network Tools window tracks the load progress.

10. Click OK to acknowledge the load completion with no errors.

11. Confirm that the LED display on the 1757-PLX52, TC-MUX021, or

1757-FIM module shows NODB.

12. Repeat the procedures in the Sections entitled Loading boot

image and Loading personality image for other 1757-PLX52,
TC-MUX021, or 1757-FIM modules in your network, as required.
Be sure to update the partner 1757-PLX52 module in an RCP
system configuration.

13. Click Network Tools

Exit to close the application. Continue

with other firmware upgrades as applicable in the next Section
or return to upgrade or installation procedures as applicable.