4-6 ProcessLogix Server Upgrade Procedures

Exporting the ProcessLogix Server Database

The following task should be performed on all system types. On
Redundant Systems, this should occur on the SERVERA Node.

1. Logon to the R320.0 system as plx_user.

2. Key in this command in the Open entry field:

>cmd<

and click OK to open the DOS window.

Station setup file The new default setup file is configured to as “static Station 1”. If this

is not correct, you must make the appropriate changes via Station’s
Setup menu.
Navigate in Knowledge Builder to

Server and Client Configuration

Guide

Configuring Stations and Printers

Using Station for

Configuration for more information.

Alarms and
messages

Alarms and messages currently in the system cannot be copied across
for the upgrade. You therefore need to resolve any alarms before
starting the upgrade

Handover notes

Handover notes in the system cannot be copied across for the
upgrade. The handover notes are therefore lost during the upgrade.

Log file

The log file found in server\data\ has now been renamed to log.txt.

History archive
search path

After upgrading, you must specify the history archive search path
using ProcessLogix Control Panel.
Navigate in Knowledge Builder to

Server and Client Configuration

Guide

Configuring Stations and Printers

Using Station for

Configuration for more information.

Custom
applications

Custom applications built for your existing system must be
re-compiled and re-linked using an appropriate development
environment.
Navigate in Knowledge Builder to

Application Development Guide

About the Development Environment

Compiling, Linking, and

Editing for more information.

Quick Builder
projects

When opening an old project file with the new version of Quick
Builder, you are prompted to migrate the project file to the new
format.

Hardware
definition files

If you want to use existing hardware definition (hdwbld) files to build
printers, you must change the CYRILLIC keyword to
LANGUAGE=CYRILLIC.

File dumps

Do not use any file dumps of the pre-upgrade database to restore the
upgraded database.