Publication 1757-IN040B-EN-P - March 2002
Supplementary Procedures 8-29
Deleting a Non-Redundant 1757-PLX52 and Unassigning its
Contents
Use the following procedure to save your existing database and delete
it from the existing non-redundant 1757-PLX52 Controller.
1. Start Control Builder.
2. Close any open Control Module and/or Sequential Control
Module.
3. In Monitoring tab, click the plus sign in the tree root path to the
non-redundant CPM being made redundant to display the CEE
folder icon.
4. Click the CEE folder icon.
5. Click Tools
⇒
Upload with Contents to upload the existing
controller database.
6. Click Continue.
This may take considerable time to complete, depending on the
amount of CM/SCMs [and their number of FBs and/or number of
Steps/Transitions] currently assigned to this CEE.
7. Click the CEE folder icon.
8. Click Tools
⇒
Update with Contents (to Project) to save the
existing controller database. Click Continue.
This may take considerable time to complete, depending on the
amount of CM/SCMs [and their number of FBs and/or number of
Steps/Transitions] currently assigned to this CEE.
9. Click the CEE folder icon.
10. Click Operate
⇒
Inactivate
⇒
This CEE’s SCMs to inactivate all
assigned SCMs, if applicable.
11. Click Yes in the dialog box to confirm the action.
12. Click Operate
⇒
Inactivate
⇒
This CEE and its IOMs and CMs to
inactivate the CEE and all assigned IOMs and CMs.
13. Click Yes in the dialog box to confirm the action.
Color of all icons changes to Blue.