Publication 1757-IN040B-EN-P - March 2002

Additional Redundant Server Procedures 6-9

4. Edit the timeserv.ini file to replace the line PrimarySource =.

with the new name of the Primary Server.

5. Click File

Save to save changes.

6. Click File

Exit to close Notepad.

7. Click Start

Run.

8. Key in this command in the Open entry field:

>timeserv -update<

and click OK to execute.

9. Click Start

Run.

10. Key in this command in the Open entry field:

>timeserv -automatic<

and click OK to execute.

11. Click Start

Run.

12. Key in this command in the Open entry field:

>net start “time service”<

and click OK to execute.

13. Click Start

Programs

ProcessLogix Server

Start-Stop

ProcessLogix Server to call up the ProcessLogix Server dialog
box.

EXAMPLE

If your Primary Server is PLX1A, the line would
become: PrimarySource=\\plx1a.

Both Servers’ time service points to SERVERA. The
file should be identical on SERVERA and SERVERB.

TIP

To display the “Full Mode” version of the
ProcessLogix Server dialog box, click the icon to the
left of ProcessLogix in the title bar and click
Advanced

Full Mode. A checkmark will now

appear in front of the Full Mode selection to show
that it is active.