Table 11.H Server redundancy specifications

Server Redundancy

Server Switchover Time – Default

30-40 sec

Server Switchover Time – Fastest Configurable Time

10 sec

On Server switchover, the 1757-PLX52 performs an event recovery. This causes the
controller to report all current alarm conditions. The Server will report all current process
alarms and events.

Table 11.I Server notification specifications

Server Notifications

Maximum number of events

(1)

(burst condition)

500 events

Maximum number of events/second

(1)

(sustained)

40/sec

Maximum number of alarms/second

(1)

(sustained)

20/sec

(1)

Up to two events are also generated for every alarm, including one event for entering the alarm condition and one for