Publication 1757-IN040B-EN-P - March 2002

Firmware Maintenance Procedures 7-15

3. Key in this command in the Open entry field:

>ntools -c -pg<

4. Click OK to launch the Network Tools application.

5. Click OK to acknowledge the warning about monitoring through

Control Builder.

6. Click Resume

to initiate network scan.

7. Click any CNB icon under the Desktop tree and wait for the

graphic of the chassis to appear in the Detail pane.

8. In the graphic of your chassis, click the CNB module with the

Network Address selected above.

9. Click Change ControlNet

to call up the Keeper Values

dialog box.

10. Confirm that the values listed for the parameters under the

Changes Tab on the dialog box match the following settings and
key in new values, as required.

TIP

If the RSLinx and PCIC driver services for system
communications in ControlNet mode are not
running, this command will start the services.

TIP

This may be the only module that appears in
the chassis graphic at this time.