11-22 Performance and Capacity Specifications

The maximum number of SST-PFBCLX modules that can be
supported by a C200 controller is 10. The modules may be
distributed in one or more downlink CNI’s. (TBD)

Multi-master configurations are supported. (TBD)

Regarding the existing limits of 64 IOM connections per CPM
and 24 IOM’s per downlink CNI:

The PBIM block is counted as 2 IOM’s

The various PROFIBUS device/module blocks that are

associated with a given PBIM are not counted in these limits.
(Only the associated PBIM is counted.)

The I/O publication/communication rate between the PBIM and
the C200 is configurable as a property of the PBIM block and
can vary between 12.5 and 50 msec.

All PROFIBUS DP baud rates are supported, up to 12 M.

Table 11.O Profibus Capacity/Topology Specifications

PFB Module and PROFIBUS Block Specifications

Note: The PROFIBUS interface module hardware component is the SST-PFBCLX, and is referred to herein
as the PFB Module. This device acts as the “master” on the PROFIBUS-DP network. Each PFB module is
represented as a block in the CEE, which is referred to as the PROFIBUS Interface Module Block (PBIM).

PROFIBUS Communication Profiles Supported

DP (only)

PROFIBUS Baud Rates Supported

12 MBps, 6 MBps, 3 MBps, 1.5 MBps, 500 KBps,
187.5 KBps, 93.75 KBps, 19.2 KBps, 9.6 KBps,

Support for Multi-Master Configurations

Yes

Support for PROFIBUS Slave Diagnostics

No

Valid PROFIBUS Station address range

0 - 125

Maximum number of modules per PBIM block
(identified by a unique station/module number
combination)

100

Maximum Input Data Size per PFB Module
(all slave stations)

496 bytes
(valid range = 4-499)

Maximum Output Data Size per PFB Module
(all slave stations)

492 bytes
(valid range = 4-495)