Chapter 2 Installation

2.3 How to Install

88

2) RCM-PST-1

Caution:

In case it is necessary to use a terminal block in an electromagnetic control box, cut off the 3P

plug to connect the line.

In that case, do not attempt to share the ground line with other devices or join with others.

For the wiring, follow the cable colors described below.

Electric wire

color

Signal Name

Description

BR

L

BL

N

Power supply

YW & GN

PE

Ground wire

Earth Terminal

Class D grounding

(Formerly Class-III grounding :

Grounding resistance at 100: or less)

Copper Wire :

Connect to a ground cable with

diameter 1.6mm (AWG14: 2mm

2

)

or more.

Ground wire

Connect it to a power socket with a grounding

electrode.

If socket is not with a grounding electrode, use a

3P-2P conversion adopter and plug into 2P

power socket. Connect the ground line to a

ground terminal near the socket.

Otherwise, cut the cable and connect it using a

terminal block in an electromagnetic control

box.

3P-2P conversion adapter

(generally purposed)

RCM-PST

Other

equipment

RCM-PST

Other

equipment

Other

equipment