Chapter 4 Operation
4.2 Operation in Positioner Mode
4.2.1 Set of Position
Table
162
11) Acceleration/deceleration mode··········Select a proper acceleration/deceleration pattern
depending on the load.
Set
Value
Acceleration/
Deceleration Pattern
Operation
0
Trapezoid
1
S-motion
(Refer to Caution at
S-shaped Motion)
Set the S-motion rate with parameter No.56.
2
First-Order
Lag Filter
Set the delay time constant with parameter No.55.
Caution at S-shaped Motion:
1) Since it requires a speed change during the operation, even if having the position
command that S-shaped motion is set while the actuator is moving, S-shaped motion
control cannot be performed and will be the trapezoid control. Make sure to make a
command while the actuator.
2) Do not use S-shaped acceleration/deceleration control if the setting of the
acceleration time or the deceleration time exceeds 2 seconds. It will not provide the
right operation.
3) Do not pause on the move during acceleration or deceleration. It will change the
speed (acceleration) and may cause a danger.
12) Incremental···············Set to 1 for pitch feed (relative movement = incremental feed).
The value set for the position in 1) indicates the pitch feed distance.
With the value set to 0, positioning is defined to the position in 1)
based on the absolute coordinate system.
Caution: In the pitch feed, do not perform a command with a pitch smaller than the
minimum encoder resolution (lead/encoder pulse number) or that less
than positioning accuracy repeatability.
There would be no deviation to occur even with the command because it
is an operation command to the same position as the positioning complete
condition, but the positioning control cannot be performed properly.
Pitch feed cannot be conducted with PIO Pattern 5 (Solenoid Valve Mode
2) of PIO Converter. Set it to “0”. Setting this to 1 causes the position data
error to occur.
Time
Velocity
Time
Velocity
Time
Velocity