7.2 Fault Diagnosis

355

[In the case of Positioner Mode]

Situation

Possible cause

Check/Treatment

Both position No. and

start signal are input to

the controller, but the

actuator does not move.

There is a problem either in PIO signal

treatment, position table setting or

operation mode selection.

1) Servo OFF condition

2) The pause signal is OFF.

3) Positioning command is issued to a

stop position.

4) There is no positioning data set to the

commanded position number.

1) Is Status LED on ERC3 turned ON

in green?

If PIO Converter is used, is Status

LED turned ON in green?

[Refer to Name for Each Parts and

Their Functions]

Turn ON the servo-on signal SON of

PIO.

2) Operation is available when PIO

pause signal *STP is ON and pause

when it is OFF. Turn it ON. [Refer to

Chapter 3, 3.1.2 and 3.3.2]

3) Check the sequence or the settings

of the position table.

4) It will generate Alarm Code 0A2

“Position Data Error”. Conduct the

position table setting.

(Note) Refer to Chapter 3 Wiring for PIO signal.