Chapter 3 Wiring

3.4 MEC Mode 1 (Operation with PLC)

126

[3] List of PIO Signals

The table below lists the functions of PIO signals. Refer to Section 4.4 [6] and [7] for the details

of the control for each signal.

Function

Stopping at 2 points

(2-point positioning)

Stopping at 3 points

(3-point positioning)

Signal

Type

Signal Name

Contents of

Signals

Movement by 1 input

between 2 points

[Single-solenoid mode]

Movement by 2 input

between 2 points

[Double-solenoid mode]

Movement by 2 input

between 3 points

[3-point positioning]

ST0

Move Signal

1

Positioning starts towards

the end point when the ON

level is detected.

Positioning starts towards

the start point when the

OFF level is detected.

ST1

Move Signal

2

Positioning starts towards

the corresponding point

when the ON level is

detected.

Moving to end point with

ST0 = OFF and ST1 = ON

Moving to start point with

ST0 = ON and ST1 = OFF

Caution

Set to [Both ON for

intermediate movement

method] in the initial

settings. Have the

interlock activated so ST0

and ST1 cannot be turned

ON at the same time. A

positioning at the

intermediate point is

performed if both are

turned ON.

Positioning starts towards

the corresponding point

when the ON level is

detected.

Moving to end point with

ST0 = OFF and ST1 = ON

Moving to start point with

ST0 = ON and ST1 = OFF

[Intermediate Point

Movement = Both ON]

Moving to intermediate

point with ST0 = ON and

ST1 = ON

Stop during operation with

ST0 = OFF and

ST1 = OFF

[Intermediate Point

Movement = Both OFF]

Moving to intermediate

point with ST0 = OFF and

ST1 = OFF

Stop during operation with

ST0 = ON and ST1 = ON

Input

RES

Reset

An alarm will be reset when this signal is turned ON.

LS0

Start Point

Detection

LS1

End Point

Detection

Not

used

LS2

Intermediate

Point

Detection

The same operation as of the sensor of the air cylinder is performed.

It is turned ON when the current position is within the positioning width for each

position detection output.

PE0

Start Point

Positioning

Complete

PE1

End Point

Positioning

Complete

P

re

ss

in

g F

un

ct

io

n

Use

PE2

Intermediate

Point

Positioning

Complete

It turns ON when the pressing or the positioning is complete.

(It also turns ON even with a miss-operation.)

It turns OFF with a movement signal to another point.

HEND

Home Return

Completion

This signal is turned ON when the home return operation is completed. This signal

will not exist when 3-point stop (3-point positioning) is selected as the operation

pattern.

Output

*ALM

Alarm Output

Signal

This signal is turned ON when the controller is in the normal condition and turned

OFF when the controller is in the alarm condition.