Chapter 6
Adjustment of Operation
6.3 I/O Parameter
6.3.2 MEC Mode 1, MEC Mode 2 and MEC Mode 3
342
(6) Press velocity (Parameter No.7)
No.
Name
Symbol
Unit
Input Range
Default factory setting
7
Press velocity
PSHV
mm/s
0.01 to actuator's
max. pressing
speed
In accordance with
actuator
This is the parameter to set the velocity in pressing operation.
If a change to the setting is required, make sure to have the setting below the maximum
pressing velocity of the actuator. Setting it fast may disable to obtain the specified pressing
force. Also when setting at a low velocity, take 5mm/s as the minimum.
Velocity
Press Velocity
Positioning width
Work
Positioning Velocity
Caution: If the velocity of the positioning of the position table is set below this
parameter, the pressing speed will become the same as the positioning
speed.
(7) Press & hold stop judgment period (Parameter No.8)
No.
Name
Symbol
Unit
Input Range
Default factory setting
8
Press & hold stop judgment
period
PSWT
msec
0 to 9999
255
Judging completion of pressing operation
Monitoring the torque (current limit) set in “Pressing Force” in the operation condition table
in %, it turns ON the pressing complete signal PE* when the load current during pressing
operation comes to the following condition. PE* turns ON once the condition is satisfied even
if the work is not stopped.
(Accumulated time in which current reaches pressing value [%])
– (accumulated time in which current is less than pressing value [%])
255 ms (Parameter No.8)
Current
Time
Pressing [%]
Operation
start
Approach end
Pressing start
200ms
20ms
75ms
295ms
200ms + 75ms – 20ms 255ms
Pressing complete (PENDoutput)
Contacting work
Decrease in current due
to movement of work