Chapter 4 Operation

4.2 Operation in Positioner Mode

4.2.2 Operation in Positioner Mode 1

188

Caution:

(1) If ST* Signal is turned ON at the same position number to repeat pitch feeding after

positioning is complete, PE* Signal turns OFF at the operation start like the positioning

in (1), and then turns back ON once the positioning is complete.

(2) If the actuator reaches the software limit (stroke end) in pitch feed, the actuator is

decelerated to be stopped and current position No. PE* is turned ON at the stop

position.

(3) PE* Signal turns ON when the actuator gets into the positioning width. Accordingly,

they may be turned ON under operation of the actuator if a large positioning width is

set.

(4) SInterlock should be taken so that two or more ST* signals are set to ON

simultaneously.

1) Entering the ST* signal of another position during positioning is invalid. If the ST*

signal of another position is turned ON during positioning, the operation is

terminated after the completion of the positioning being operated.

2) Entering the ST* signal of another position with the ST* signal of the current position

remaining ON after the completion of positioning allows the positioning to the other

position to be executed.

(5) If Parameter No.27 “Move command type” is set to “0” (factory setting), turning ST*

OFF during positioning caused the operation to be interrupted.

(6) Note that, when Parameter No.27 “Move command type” is set to “1”, starting (ST* ON)

pitch feed repeatedly during pause causes the actuator to be moved successively by

the number of starts. If this situation is supposed, cancel the remaining moving

distance by turning reset signal RES ON in the pause state or take interlock so that

start signals are not turned on during pause.

(7) The pressing operation is enabled by using the pitch feed function.

(8) In the pitch feed, do not perform a command with a pitch smaller than the minimum

encoder resolution (lead / encoder pulse number) or that less than positioning accuracy

repeatability.

There would be no deviation to occur even with the command because it is an

operation command to the same position as the positioning complete condition, but the

positioning control cannot be performed properly.