Chapter 6

Adjustment of Operation

6.3 I/O Parameter

6.3.2 MEC Mode 1, MEC Mode 2 and MEC Mode 3

343

(8) Current limit value at stopping due to miss-pressing (Parameter No.9)

No.

Name

Symbol

Unit

Input Range

Default factory setting

9

Current limit value at

stopping due to

miss-pressing

PSFC

0: Current limiting

value at stop

1: Current limit

value during

pressing

0

This parameter defines the restricted current value at stopping due to miss-pressing.

This restricted current value locks the servo till the next moving command.

(9) Auto servo motor OFF delay time (Parameter No.10)

No.

Name

Symbol

Unit

Input Range

Default factory setting

10

Auto servo motor OFF delay

time

ASO1

sec

0 to 9999

1

Set the duration before the servo turns OFF after positioning process is complete when the

power saving function is used.

[Refer to Chapter 5 Power-saving Function.]

(10) Stop mode selection (Parameter No.11)

No.

Name

Symbol

Unit

Input Range

Default factory setting

11 Stop mode selection

CTLF

0: Full stop

1: Servo-motor stop

0 (Does not use)

This parameter defines the power-saving function.

For complete stop, the actuator stops with the servo being on.

For servo stop, it stops with the full servo control.

[Refer to Chapter 5 Power-saving Function.]

(11) Current-limiting value at standstill during positioning (Parameter No.12)

No.

Name

Symbol

Unit

Input Range

Default factory setting

12

Current-limiting value at

standstill during positioning

SPOW

%

1 to 70

35

When the value is increased, the stop holding torque is increased.

It is not necessary to change this setting in normal use. Movement due to external force can be

prevented by setting the value bigger in case a large force is applied during a stop. However,

there is a risk that motor or controller may burn if the setting is too high. Please contact IAI.

(12) Current-limiting value during home return (Parameter No.13)

No.

Name

Symbol

Unit

Input Range

Default factory setting

13

Current-limiting value during

home return

ODPW

%

1 to 100

In accordance with

actuator

The factory setting conforms to the standard specification of the actuator.

Increasing this setting will increase the home return torque.

It is not necessary to change this setting in normal use. Home-return operation may complete in

front of the proper point in some cases depending on how it is installed or load is attached when

the product is vertically mounted. It is necessary to increase the setting value in such cases.

Other causes can also be considered, so contact us in advance to making a change.