Chapter 7

Troubleshooting

7.2 Fault Diagnosis

353

7.2 Fault Diagnosis

This section describes faults largely divided into three types as follows:

(1) Impossible operation of controller

(2) Positioning and speed of poor precision (incorrect operation)

(3) Generation of noise and/or vibration

7.2.1 Impossible operation of controller

Situation

Possible cause

Check/Treatment

1) Positioner Mode 1.

Pulse Train Control

Mode

Status Display LED

does not turn ON in

green even though

the power to ERC3 is

supplied in MEC

Mode 1 or MEC Mode

2.

2) Positioner Mode 2.

SV in Status Display

LEDs does not turn

ON even though the

power to PIO

Converter is supplied

in MEC Mode 2.

(1) Proper power is not supplied.

(2) Servo-on command PIO is not input

to ERC3 and PIO converter.

1) Poor contact of flat cable

(3) Occurrence of alarm.

(4) During emergency-stop.

1) Was the emergency-stop switch

released?

2) Positioner Mode 1, MEC Mode 1,

Pulse Train Control Mode

EMG on the ERC3 is not

connected.

3) Positioner Mode 2, MEC Mode 2

EMG- on the power supply

connector of PIO Converter is

disconnected.

4) MEC Mode 3

The wiring of the emergency stop

connector on Quick Teach is

disconnected.

(1) Ensure that appropriate voltage is

supplied and the wiring is in the right

condition.

[Refer to Chapter 3, 3.1.3 [1], 3.2.3

[1], 3.3.3 [1], 3.4.3 [1] and 3.5.3 [1]

wiring of Power Line and

Emergency Stop Circuit.]

(2) 1) Are the PIO cable connectors

inserted to the mating connectors

securely? Check the input signals

on the I/O monitor of the teaching

tool such as PC software.

Caution

In I/O cable conduction check, do not

widen female pins of the connectors.

Failure to follow this may cause poor

contact.

(3) Check the error code with the

teaching tool being connected and

remove the cause by referring the

alarm list.

[Refer to 7.4 Alarm List.]

(4) 1) Release the emergency stop

switch.

2) Positioner Mode 1, MEC Mode 1,

Pulse Train Control Mode

Check the connection of wires on

EMG of ERC3.

3) Positioner Mode 2, MEC Mode 2

Check the connection of wires on

PIO Converter power supply

connector EMG-.

[Refer to Chapter 3, 3.1.3 [1],

3.2.3 [1], 3.3.3 [1], 3.4.3 [1] and

3.5.3 [1] wiring of Power Line and

Emergency Stop Circuit.]

4) Check the wiring of the

emergency stop connector on

Quick Teach. If it is not to be

used, have the enclosed plug

connector to make short-circuit.