Chapter 6 Adjustment of Operation
6.1 Absolute Reset and Absolute Battery
6.1.1 Absolute Reset
PIO Converter is necessary for Simple Absolute Type. Simple Absolute Type retains the
encoder position information in the battery backup. It is not necessary to perform the
home-return operation every time the power is turned ON.
In order to hold the encoder position information, absolute reset is required.
Provide absolute reset in the following cases:
(1) Initial activation
(2) When the absolute battery was replaced with the power to the PIO converter is shut, and
(3) When disconnected the power supply and I/O cable for the actuator from PIO Converter
The absolute reset is performed by using a teaching tool such as PC software or PIO. The
absolute reset using PIO is available in Positioner Mode 2. Also, the absolute reset cannot be
performed on Quick Teach.
Caution: If it is Pulse Train Control Mode, it would not comply with simple
absolute type. Take the greatest care.
[1] Absolute reset procedure from teaching tool
(1) For PC software
1) Connect the actuator with the PIO converter. [Refer to Chapters 3.]
2) Connect the absolute battery (Enclosed battery if starting up for the first time, new battery
if replacing) to the absolute battery connecting connector on the bottom of the PIO
converter. [Refer to 6.1.1 [3].]
3) Connect PC, turn the power ON to PIO Converter and start up RC PC software.
4) Alarm 0EE “Absolute Encoder Error Detection 2” is shown. Select position data from main
window and press Alarm button to conduct alarm reset.
5) Select position data from main window and press Home button to have a home-return.
Once the home return is complete, the point of origin is memorized at the same time the
origin point is established.