3 circuit diag, 1] power line and emergency stop circuit, 3 circuit diagram – IAI America ERC3 User Manual
Page 124
Chapter 3 Wiring
3.3 Positioner Mode 2 (Extension
Type by PIO Converter)
114
3.3.3 Circuit Diagram
Sample circuit diagrams are shown below.
[1] Power Line and Emergency Stop Circuit
(1) Built-in Drive Cutoff Relay Type
Note 1 When the teaching pendant is not connected, S1 and S2 become short-circuited inside the
controller.
Note 2 For CR1, select the one with coil current 0.1A or less.
Note 3 This circuit is equivalent to Safety Category 1.
The load current for the emergency stop signal EMG (-) to turn ON/OFF at contact CR1 is 24V
DC and 20mA.
Caution:
• Do not attempt to cut the 0V circuit of GND whit the emergency stop. Doing so may burn the
internal circuit. If an absolute shutoff of the power supply is required, conduct it on the primary
side of DC power supply (alternating current side).
• In case the power source for each controller is different, join the 0V of each power supply
together.