IAI America ERC3 User Manual
Page 342
Chapter 6
Adjustment of Operation
6.3 I/O Parameter
6.3.1 Positioner Mode 1, Positioner Mode 2 and Pulse
Train Control Mode
332
(67) Total operated distance threshold (Parameter No.148)
No.
Name
Symbol
Unit
Input Range
Default factory setting
148 Total operated distance
threshold
ODOT
m
0 to 999999999
0 (Disabled)
Notice will be made with Movement Distance Threshold Exceeding Alarm (04F) if the total
distance of movement exceeds the value set in this parameter.
The judgment would not be made if the value is set to 0.
(68) Zone output changeover (Parameter No.149)
No.
Name
Symbol
Unit
Input Range
Default factory setting
149 Zone output changeover
FPIO
–
0: Not to change
1: To change
0
The enable zone signals are determined by the setting of this parameter and the setting of
Parameter No.25 “PIO Pattern Select”.
The relationship between the parameter settings and enable zone signal outputs are as shown
in the table below.
Parameter No.149 Zone Output Changeover
Operating Mode
Parameter No.25
PIO Pattern Selection
0
1
0
ZONE1 no matter settings
1
There are no zone outputs
Positioner Mode 1
2
PZONE
ZONE1
0
ZONE1
PZONE
ZONE1
ZONE2
1
2
PZONE
ZONE1
3
There is no zone signal output
4
Positioner Mode 2
5
ZONE1
PZONE
ZONE1
ZONE2
Pulse Train Mode
There is no zone signal output
(69) High output setting (Parameter No.152)
No.
Name
Symbol
Unit
Input Range
Default factory setting
152 High output setting
BUEN
–
0: Disable
1: Enable
1 (Enabled)
Establish the setting of enable/disable for the high output function.