HP Array Controller HSG V8.7 Software User Manual
Page 77
Configuring an HSG80 Array Controller
2–23
Table 2–6 Key to Figure 2–9 Cabling for Dual-Redundant
Configuration with One Hub using Fibre Channel
Optical Support
1. Stop all I/O from the host to its devices on the bus to which you are
connecting the controllers.
2. For this configuration, set Port 2 off-line using the SET
THIS_CONTROLLER PORT_2_TOPOLOGY=OFFLINE command.
See Appendix B, “CLI Commands,” for details about the SET
command.
3. Connect the Fibre Channel cable from Port 1 on controller A to Port 9
on hub 1. Repeat this step to connect the second cable from Port 1 on
controller B to Port 8 on hub 1.
4. Connect another Fibre Channel cable from Port 2 on controller A to Port
1 on hub 2. Repeat this step to connect the final cable from Port 2 on
controller B to Port 2 on hub 2.
5. Connect each hub to their respective host according to the instructions
supplied in the Getting Started manual.
6. Route and tie the cables as desired.
7. Restart the I/O from the host. Some operating systems may require you
to restart the host to see the devices attached to the new controller.
Item Description
Part
No.
1
Dual Controller
—
2
12-Port Fibre Channel HUB
DHGGA-CA
3
.5 M Fibre Channel Optic cable
1 M Fibre Channel Optic cable
2 M Fibre Channel Optic cable
3 M Fibre Channel Optic cable
5 M Fibre Channel Optic cable
10 M Fibre Channel Optic cable
20 M Fibre Channel Optic cable
30 M Fibre Channel Optic cable
50 M Fibre Channel Optic cable
100 M Fibre Channel Optic cable
200 M Fibre Channel Optic cable
400 M Fibre Channel Optic cable
17–04820–01
17–04820–02
17–04820–03
17–04820–04
17–04820–05
17–04820–06
17–04820–07
17–04820–08
17–04820–09
17–04820–10
17–04820–11
17–04820–12