Input points—pre-defined sensor types, Burglary points, Life/safety points – Interlogix VEREX Director User Manual
Page 277: Supervisory points, Local points
21-0381E v4.9.1
Welcome Report Control Admin
Sys Config
Tech-Ref
269
Input Points—Pre-Defined Sensor Types
Burglary Points:
Type Arming
Level
Preprocess
Class
By-
pass
Chime
Tx
Off
Tx
Stay
Tx
On
Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
Entry
Door Perimtr Door
(area
1)
Burg
--
--
--
--
Entry Route
12hr
E/E Route
Burg
--
--
--
-- --
Perimeter Perimeter
Immed Burg
--
--
--
Interior Motion
12hr
Immed
Burg
--
--
--
--
-- --
FAP - Motion
12hr
FAP
Burg
--
--
--
--
-- --
Day Warning
24hr
Immed
Burg
--
--
-- --
24hr Burglary 24hr
Immed
Burg
--
Life/Safety Points:
Type Arming
Level
Preprocess
Class
By-
pass
Chime Tx Off
Tx
Stay
Tx On Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
Fire - A 24hr Immediate
Fire-A
Fire 24hr
15s
delay Fire
Fire 24hr
Immediate
Fire
Hold-up 24hr Immediate
holdup
Aux Alert
24hr
Immediate
Emerg
Supervisory Points:
Type Arming
Level
Preprocess
Class
By-
pass
Chime Tx Off
Tx
Stay
Tx On Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
Supervisory 24hr
Immediate Spvsr
Battery Fail
24hr
Battery Fail
Spvsr
Mains Fail
24hr
Mains Fail
Spvsr
Local Points:
Type Arming
Level
Preprocess
Class
By-
pass
Chime
Tx
Off
Tx
Stay
Tx
On
Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
Local - 24hr
24hr
Immed
Burg
Local-Stay&On Perimeter Immed
Burg
Local-
Stay2 & ON
Perimeters Immed
Burg
Local -
ON only
12 hr
Immed
Burg
Legend:
The 'Class' setting determines the type of alarm message to be transmitted;
Bypass means whether or not the input point will be bypassable;
Chime pertains to whether or not the triggering of the input will cause audible tones at keypads in the
area (normally used with Entry points/routes to let you know that someone has entered);
Tx Off, Stay, and On pertain to the arming levels for which activation of the input point will cause an
alarm to be transmitted to the monitoring station;
Sonlrt Off, Stay, and On pertain to the arming levels for which activation of the input point will cause
keypad 'sonalerts' in the area to be sounded for one second.
Siren Off, Stay, and On pertain to the arming levels for which activation of the input point will cause
siren outputs in the area to be sounded.