Screen reference, Area users (activity, user count, and apb-reset) – Interlogix VEREX Director User Manual
Page 104

96
Verex Director V4.9.1 User's Guide
21-0381E v4.9.1
Control & Status - Area Users
The "Area Users" screen shows / allows:
Whether or not activity has occurred in the
area.
(This is based on users entering or leaving the
area, and/or a custom 'Activity Monitor' input point
being tripped.)
The number of users presently in the area;
Whether or not the area is full (i.e., contains
the 'allowed' number of persons/vehicles).
Allows resetting the 'user-count' as desired
(to min/empty, max. allowed, or any custom
value);
Allows resetting the antipassback (APB)
status for all users in an area
(see next
section)
.
Note: To be available here, the 'user-counting' and
'activity tracking' features must have been set up for the
specific area(s).
Ref: "Configuration Areas" (Counting; Activity).
Working with this Screen
Ensure you are connected with the specific
panel(s) as described previously.
Open the
Area Users
screen:
MyTools Bar: Control & Status - Area Users
Tree: Control & Status, Panel Control & Status,
Areas, Area Users
Use the
Grid
/
Form
toolbar-button to select
your preferred view-mode;
Refer to the selection-descriptions for this
screen while viewing the status topics for
items in the desired area.
Screen Reference
- Area (bottom of form): This is where you select
an area to view its status or control items. This
shows a reference number assigned by the
system, plus the name/description of the area as
defined under 'Configuration'.
Status
- Activity in Area: Whether or activity has
occurred in the specific area. (This is based on
users entering or leaving the area, and/or a
custom 'Activity Monitor' input point being
tripped.)
- User Count: This is the number of users (or
vehicles) in the area (based on access granted
in to and out of the area).
Full: Whether or not the area contains the allowed
number of users/vehicles.
- [ Reset User Count ]: This allows resetting this
area's user-count as desired. (Details to follow /
below.)
Anti-Passback
- [ APB Reset ]: This allows resetting the
antipassback status pertaining to the selected
area, for all users. (Details to follow / below.)
Confirm/Unconfirm Alarm
(UK/ACPO Panel Mode)
- Confirmed Alarm: This indicates if there are
any confirmed alarms in the selected area;
- Unconfirmed Alarm: This indicates if there are
any uncomfirmed alarms in the selected area;
- [ Reset Confirmed Alarm ]: This allows
resetting all confirmed alarms in the selected
area.
Notice: The UK ACPO standard includes strict
requirements regarding confirmed vs. unconfirmed
alarms, and resetting alarms. Interested parties are
expected to be familiar with such details. Installation
requirements can be found in a UK/ACPO appendix of
the advanced installation guide for your specific
panel(s).
Area Users (Activity, User Count, and APB-Reset)
Control & Status Panel Control & Status
Areas Area Users