Expansion Modules and Related
Settings
Expansion modules are devices that provide
support for additional inputs, outputs, and/or
special features. Some examples include:
System LCD keypads (different types—some
with built-in reader);
Door Controllers (typically supporting
2 doors / 4 readers);
Elevator / Lift Controller (2 cabs, with one
reader per cab; max. 124 floors);
Point Expander (8 or 16 input points;
and 4 programmable outputs);
RF / Wireless Point Expansion (32 inputs);
Fire Supervision module;
Map/Graphic Annunciator;
High-security comms / printer module
(uses Mark7 / DVACS service in Canada).
Power supply: Intelligent monitorable power
supplies;
For each panel, up to 24 modules can be set up (or up
to 60 suite-security keypads), including support for up
to 32 doors.
Converted TDC/PDC Door Controller Modules: Up to
10 (combined) per system panel.
Note: To initially set up a system module, you will need
to know its serial number. This is typically hand-written
on a small sticker on the circuit board).
Attention: Some modules (HSC/printer module,
RF/wireless module, and Smart POD) require additional
programming locally, through a system keypad. For
details, refer to the commissioning or hardware guide
for your system.
How to Get Here
Multi-Account Systems: First select [Account Folders]
in the 'tree', and locate and double-click the desired
account.
MyTools Bar: Modules
In the Tree: Configuration
(click the "+")
,
Modules
(Under the specific panel group and
panel--if listed in the 'tree'.)
Related Topic: "Other Desktop Choices".
Tip: The Grid / Form toolbar-button allows selecting
your preferred view-mode (forms view is recommended
here).
Things You Can Do
Add a Module: Click [+] at the bottom of the
form, or right-click the form and select Add
New from the pop-up menu.
View/Change an Existing One: Select one
from the pop-up list at the bottom of the
form.
Search for a Module: Click the 'binoculars'
symbol. Then, enter the name and click
[Find].
Tip: You can search by name or the 1
st
few
characters--e.g., nam*
Delete a Module: Right-click a blank area
on the form (
If grid view: Right-click the item in
the list
), and select "Delete". When prompted
to confirm, select Yes.
Before Deleting: If a module is deleted, or changed
with respect to the number of points or outputs, the
I/O range adjusts accordingly. As such, all
points/outputs pertaining to this expansion-module
number and higher will need to be reconfigured.
As well, only modules NOT presently associated with
any doors can be deleted. (Issue a report, OR go to
the Door configuration topic, select Grid view, and
look for the specific module.)
Related Topic(s):
Reporting on Users, System/Device Settings, etc.;
Working with the Report Viewer
Working in Grid View: You can:
View or enter values;
Right-click an item and select from the pop-up menu;
Click a column heading to sort on that column.
(Filter on Column: Shows only items matching an
entered value or 1
st
few chars.--e.g., nam*. A red
column heading indicates the list is filtered.)
If a Module is Replaced
If a defective or damaged module is replaced,
be sure to identify the new module's "Serial
Number" to the software. (See the "Serial
Number" description for details.)
-------------------------
Then, issue a "Send to Panel" communications
session to transfer all settings to the
associated panel.
For details, refer to "Panel Communications and
Updates".