To have the door simply re-lock at the closing time, set
the "In Schedule" value as desired, and set the "Out of
Schedule" value to "Locked".
To have the door unlocking follow the area arming-
state only, set the schedule to "None", and "In
Schedule" to either "Area is Off", or "Area is
Stay/Off", as desired.
If you do not want the door to unlock automatically
based on a schedule and/or the area arming-state, set
the "Schedule" to "None", and the 'In Schedule' value
to "Locked".
Circuit
With converted TDC/PDC door controllers, this setting
does not apply.
- Reader Tamper Circuit: This is the type of
circuit/wiring used with the reader tamper circuit
for this door.
Not Required: This disables the reader tamper input
(i.e., the tamper input will not be monitored).
Converted TDC/PDC Door Controllers: These units
do not support dedicated/separate reader tamper
monitoring.
- Door Circuit: This is the type of circuit/wiring
used with the door contact for this door.
-------------------------
- Process Reader Tamper as Input Point:
Future use.
Other
- Door Arming Level: The area arming levels
for which the door is to be monitored.
Tip: You may wish to use "Stay and On" with doors
used to enter the facility, and "On Only" for all doors
within the facility.
- Bi-Colour LED Mode: Select this if the reader
at this door has a single bi-color LED (instead of
the two separate LEDs). This setting
must
also
be used if an 'arming station' is present.
Note: Arming-station wiring differs from other readers
(ensure the proper installation instructions have been
followed).
- Entry Detect: If selected (), persons will not
be considered "In" the new area if they are
granted entry, but do not open the door.
Tip: This affects the in/out status of applicable users,
and allows them to badge again to gain entry with
antipassback turned on (see "Detect Antipassback", to
follow / below).
Related: Configuration Areas
Counting and Auto Arm.
Note: This does NOT affect 'Activity' detection
(Cfg.Areas Activity).
- Disable *30 – Arm All Areas: (Director ≥
v4.80) Select this to disable arming all areas in
readers assigned to chosen doors.
Note: The XL Panel ≥ 4.58g is required.