9440500990 Rev D

71

DECS-250N

Metering

Figure 59. Power Primary-Values

Figure 60. Energy

When operating in motor mode, values for var and power factor will be opposite in BESTCOMSPlus and
on the front-panel HMI. See Table 4.

Table 4. Operating Mode

Sign of Vars

DECS-250 Operating Mode

Generator

Motor

Positive (+)

Leading PF

Lagging PF

Negative (

–)

Lagging PF

Leading PF

Bus

BESTCOMSPlus Navigation Path: Metering Explorer, Bus

HMI Navigation Path: Metering Explorer, Bus

Metered bus parameters include the voltage across phases A and B (Vab), phases B and C (Vbc),
phases A and C (Vca), and the average bus voltage. The frequency of the bus voltage is also metered.
Primary- and per-unit values are available. Figure 61 illustrates the bus primary-values metering screen.