beautypg.com

Modbus™ communication, Rs-485 port, Modbus ™ communication – Basler Electric DECS-250N User Manual

Page 180

background image

164

9440500990 Rev D

Communication

DECS-250N

Modbus

™ Communication

BESTCOMSPlus Navigation Path: Settings Explorer, Communications, Modbus Setup

HMI Navigation Path: Not available through HMI.

DECS-250N systems support the RS-485 mode and Modbus/TCP (Ethernet) mode at the same time.
DECS-250N Modbus communication registers are listed and defined in the Modbus Communication
chapter of this manual.

Modbus settings for RS-485 and Ethernet are illustrated in Figure 138 and consist of RS-485 Unit ID

A

,

RS-485 Response Delay

B

, and Ethernet Unit ID

C

.

Figure 138. Modbus Setup

A

RS-485 Unit ID: Adjustable from 1 to 247 in increments of 1.

B

RS-485 Response Delay: Adjustable from 10 to 10,000 ms in 10 ms increments.

C

Ethernet Unit ID: Adjustable from 1 to 247 in increments of 1.

RS-485 Port

BESTCOMSPlus Navigation Path: Settings Explorer, Communications, RS-485 Setup
HMI Navigation Path: Settings, Communications, RS-485 Setup

An RS-485 port uses the Modbus RTU (remote terminal unit) protocol for polled communication with other
networked devices or remote annunciation and control with an IDP-800 Interactive Display Panel. RS-485
port terminals are located on the left side panel and are identified as RS-485 A, B, and C. Terminal A
serves as the send/receive A terminal, terminal B serves as the send/receive B terminal, and terminal C
serves as the signal ground terminal. Figure 139 illustrates typical RS-485 connections for multiple
DECS-250N controllers communicating over a Modbus network.

This manual is related to the following products: