Protection

during overexcitation. The field current must fall below the dropout ratio (95%) for the function to begin
timing to reset. The following equations are used to calculate the field overcurrent pickup and reset time
delays.

𝑡

𝑝𝑖𝑐𝑘𝑢𝑝

=

𝐴 × 𝑇𝐷

𝐵 + √𝐶 + 𝐷 × 𝑀𝑂𝑃

Equation 9. Inverse Field Overcurrent Pickup

Where:
t

pickup

= time to pick up in seconds

A

= -95.908

B

= -17.165

C

= 490.864

D

= -191.816

TD

= time dial setting <0.1, 20>

MOP = multiple of pickup <1.03, 205>

𝑇𝑖𝑚𝑒

𝑟𝑒𝑠𝑒𝑡

=

0.36 × 𝑇𝐷

(𝑀𝑂𝑃

𝑟𝑒𝑠𝑒𝑡

)

2

− 1

Equation 10. Inverse Field Overcurrent Reset

Where:
Time

reset

= maximum time to reset in seconds

TD

= time dial setting <0.1, 20>

MOP

reset

= multiple of pickup <1.03, 205>

Primary and secondary setting groups provide additional control for two distinct machine operating
conditions.

Field overcurrent protection can be enabled and disabled

E

without altering the pickup and time delay

settings. Field overcurrent pickup and trip elements in BESTlogicPlus can be used in a logic scheme to
initiate corrective action in response to the condition. BESTCOMSPlus field overcurrent settings are
illustrated in Figure 37. In BESTCOMSPlus, a plot of the field overcurrent setting curve is displayed. The
plot can display the primary or secondary setting curves.