180
9440500990 Rev D
Security
DECS-250N
4.
Enter the desired password for the user
C
.
5.
Reenter the password created in step 4 to verify the password
D
.
6.
Select the maximum allowed access level
E
for the user.
7.
If a maximum duration is desired for the user’s access, enter the limit
F
(in days). Otherwise, leave
the expiration value at zero.
8.
Click the Save User button
G
to save the user settings.
9.
Open the Communication menu, and click Upload Security to Device.
10.
BESTCOMSPlus notifies you when the security upload is successful.
Figure 155. Password Access Settings
A
User List: Displays 26 usernames and the corresponding maximum access levels.
B
User Name: Accepts up to a 16 character label that may include upper and lowercase letters, numbers,
and special characters.
C
Password: Accepts up to a 16 character label that may include upper and lowercase letters, numbers,
and special characters.
D
Verify Password: Accepts up to a 16 character label that may include upper and lowercase letters,
numbers, and special characters.
E
Maximum Access Level Allowed: Select Read, Control, Operator, Settings, Design, or Admin.
F
Days to Expiration: Adjustable from 0 to 50,000 days in 1 day increments. 0 disables setting.
G
Save User: Click button to save username and password settings.
Port Security
BESTCOMSPlus Navigation Path: Settings Explorer, General Settings, Device Security Setup, Port
Access Setup
An additional dimension of security is provided by the ability to restrict the control available through the
DECS-250N communication ports. At any given time, only one port can be in use with read or higher
access. For example, if a user gains settings access at one port, users at other ports will be able to gain
no higher than read access until the user with settings access logs off. This screen cannot be accessed
when in Live Mode.