9440500990 Rev D

227

DECS-250N

Modbus™ Communication

Name

Register

Type

Bytes

R/W

Unit

Range

Droop Value

42280

Float

4

R W

Percent

0 - 30

L-Drop Value

42282

Float

4

R W

Percent

0 - 30

Auxiliary Limit Enable

42284

Int32

4

R W

n/a

Disabled=0 Enabled=1

Field Current Regulation Pre-position
Mode 3

42286

Uint32

4

R W

n/a

Maintain=0 Release=1

Field Current Regulation Pre-position 3

42288

Float

4

R W

Amp

Setpoint adjustment range determined
by registers 42212 and 42214.

Generator Voltage Pre-position Mode 3

42290

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator Voltage Pre-position 3

42292

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42228 and 42230.

Generator var Pre-position Mode 3

42294

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator var Pre-position 3

42296

Float

4

R W

kilovar

Setpoint adjustment range determined
by registers 42244 and 42246.

Generator PF Pre-position Mode 3

42298

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator PF Pre-position 3

42300

Float

4

R W

Power Factor

Setpoint adjustment range determined
by registers 42260 and 42262.

FVR Pre-position Mode 3

42302

Uint32

4

R W

n/a

Maintain=0 Release=1

FVR Pre-position 3

42304

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42276 and 42278.

Active Field Current Regulation Setpoint

42306

Float

4

R W

Amp

Setpoint adjustment range determined
by registers 42212 and 42214.

Active Generator Voltage Setpoint

42308

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42228 and 42230.
When the With Limits box is checked on
the Auxiliary Input screen in
BESTCOMSPlus, register 42308 equals
register 42216 plus the Aux input.
When the With Limits box is not
checked on the Auxiliary Input screen in
BESTCOMSPlus, register 42308 equals
register 42216.

Active Generator var Setpoint

42310

Float

4

R W

kilovar

Setpoint adjustment range determined
by registers 42244 and 42246.

Active Generator PF Setpoint

42312

Float

4

R W

Power Factor

Setpoint adjustment range determined
by registers 42260 and 42262.

Active FVR Setpoint

42314

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42276 and 42278.

Transient Boost Enable

42316

Int32

4

R W

n/a

Disabled=0,Enabled=1

Transient Boost, Fault Voltage
Threshold

42318

Float

4

R W

Percent

0 – 100

Transient Boost, Fault Current
Threshold

42320

Float

4

R W

Percent

0 – 400

Transient Boost, Minimum Fault
Duration

42322

Float

4

R W

Second

0 – 1

Transient Boost, Voltage Setpoint
Boosting Level

42324

Float

4

R W

Percent

0 – 100

Transient Boost, Clearing Voltage
Threshold

42326

Float

4

R W

Percent

0 – 50

Transient Boost, Clearing Voltage Delay

42328

Float

4

R W

Second

0 – 1

Global Settings

Table 30. Global Settings Group Parameters

Group

Name

Register

Type

Bytes

R/W

Unit

Range

PLC Timed Element Settings

Logic Timer 1 Output Timeout

42400

Float

4

R W

Sec

0 - 1800

PLC Timed Element Settings

Logic Timer 2 Output Timeout

42402

Float

4

R W

Sec

0 - 1800

PLC Timed Element Settings

Logic Timer 3 Output Timeout

42404

Float

4

R W

Sec

0 - 1800

PLC Timed Element Settings

Logic Timer 4 Output Timeout

42406

Float

4

R W

Sec

0 - 1800

PLC Timed Element Settings

Logic Timer 5 Output Timeout

42408

Float

4

R W

Sec

0 - 1800

PLC Timed Element Settings

Logic Timer 6 Output Timeout

42410

Float

4

R W

Sec

0 - 1800