9440500990 Rev C

Introduction

DECS-250N

Twelve contact outputs

o

One, fixed-function output: Watchdog (SPDT configuration)

o

Eleven programmable outputs

Flexible communication

o

Serial communication through front-panel USB port

o

Modbus communication through RS-485 port or Modbus TCP

o

Ethernet communication through an optional copper or fiber optic port

o

CAN communication with an ECU (engine control unit), optional AEM-2020 Analog
Expansion Module, or optional CEM-2020 Contact Expansion Module

o

Optional PROFIBUS communication protocol

Data logging, sequence of events recording, and trending

Optional CEM-2020 Contact Expansion Module provides:

o

Ten contact inputs

o

Eighteen contact outputs (CEM-2020H) or 24 contact outputs (CEM-2020)

o

Customizable input and output functions assigned through BESTlogic™Plus
programmable logic

o

Communication via CAN protocol

Optional AEM-2020 Analog Expansion Module provides:

o

Eight analog inputs

o

Eight resistive thermocouple device (RTD) inputs

o

Two thermocouple inputs

o

Four analog outputs

o

Customizable input and output functions assigned through BESTlogicPlus programmable
logic

o

Communication via CAN protocol

Applications

The DECS-250N is intended for synchronous generator or synchronous motor applications. The DECS-
250N controls the machine output through the application of regulated DC excitation power to the exciter
field. The level of excitation power is based on the monitored voltage and current, and a regulation
setpoint established by the user. The operating mode, generator or motor, is changed on the Operating
Mode settings screen. Power factor and var metering values will be opposite in motor mode.

Excitation power is supplied from the DECS-250N by means of a six-SCR, full-wave bridge. It is capable
of two-quadrant operation; it can produce negative as well as positive output power. With nominal
operating voltage applied, the DECS-250N is capable of supplying 20 Adc continuously at a nominal
voltage of 32, 63, or 125 Vdc.

Package

A single, compact package contains all excitation control and power components.

A front panel HMI provides local annunciation and control through a backlit liquid crystal display (LCD),
light-emitting diodes (LEDs), and pushbuttons. Remote annunciation and control is provided through a
flexible communication interface which accommodates Ethernet, Modbus, optional PROFIBUS, and the
optional Interactive Display Panel (IDP-800).

Optional Features and Capabilities

DECS-250N optional features and capabilities are defined by a combination of letters and numbers that
make up the style number. The model number and style number describe options and characteristics in a
specific device and appear on a label affixed to the device.

This manual is related to the following products: