DECS-250N
BESTlogic
™Plus
Name
Description
Symbol
NTP Sync Lost
True when NTP server has lost communications.
Null Balance
True when Null Balance is achieved in both
external and internal tracking.
OEL
True when the Overexcitation Limiter is active.
PF Controller
Active
True when the unit is in PF mode.
PLL Sync
Selected
True when phase locked loop (PLL) is selected.
(Synchronizer screen)
Preposition
Active
True when any preposition is active.
Preposition 1
Active
True when Preposition 1 is active.
Preposition 2
Active
True when Preposition 2 is active.
Preposition 3
Active
True when Preposition 3 is active.
PSS Active
(Optional)
True when the power system stabilizer (PSS) is
turned on and running.
PSS Current
Unbalanced
(Optional)
True when the phase current is unbalanced and
the PSS is active.
PSS Power
Below Threshold
(Optional)
True when the input power is below the Power
Level threshold and the PSS is active.
PSS Secondary
Group (Optional)
True when the PSS is using secondary settings.
PSS Speed
Failed (Optional)
True when the frequency is out of range for a
length of time calculated internally by the DECS-
250N and the PSS is active.
PSS Test On
(Optional)
True when the power system stabilizer test signal
(Frequency Response) is active.
PSS Voltage
Limit (Optional)
True when the calculated terminal voltage upper or
lower limit is reached and the PSS is active.
PSS Voltage
Unbalanced
(Optional)
True when the phase voltage is unbalanced and
the PSS is active.
SCL
True when the Stator Current Limiter is active.
Setpoint at Lower
Limit
True when the active modes setpoint is at the lower
limit.