Table 5 – Basler Electric DECS-250N User Manual
Page 133
![background image](https://www.manualsdir.com/files/773924/content/doc133.png)
9440500990 Rev D
117
DECS-250N
Terminals and Connectors
Table 5. Left Side Terminal and Connector Descriptions
Locator
Description
A
These terminals accept three-phase operating power for the excitation power stage of
the DECS-250N. A ground for the operating power connections is provided at terminal
GND.
B
Excitation power is supplied to the field through the terminals labeled F+ and F–. The
GND terminal serves as the chassis ground for the DECS-250N.
C
These terminals connect to user-supplied current transformers (CTs) providing three
phases of generator sensing current and a cross-current compensation signal.
D
These terminals accept ac and/or dc control power to enable DECS-250N operation.
A ground terminal is also provided.
E
Three-phase generator and bus sensing voltage, obtained from user-supplied voltage
transformers (VTs), connect to these terminals.
F
A portion of this terminal block accepts an external analog control signal for auxiliary
control of the regulation setpoint. Terminals I+, I–, V+, and V– are used for external
control of the regulation setpoint with the GND terminal serving as a cable shield
connection.
The remaining terminal block pins serve as connections for the Watchdog and
programmable relay outputs 1 through 4.
G
Relay contact outputs for programmable relay outputs 4 through 11 connect to these
terminals.
H
Contact inputs for the Start and Stop functions and programmable contact inputs 1
through 4 are applied to these terminals.
I
Programmable contact inputs 5 through 10 are applied to these terminals.
J
A portion of these terminal block pins accept connections for programmable contact
inputs 11 through 14.
The remaining terminal block pins serve as connections for RS-485 communication.