9440500990 Rev D

209

DECS-250N

Modbus™ Communication

Group

Name

Register

Type

Bytes

R/W

Range

Time

Time

40169

String

16

R

0 - 16

Unit Information

Style Number

40177

String

32

R

0 - 32

Unit Information

Serial Number

40193

String

32

R

0 - 32

DECS Control

Control Output Var PF

40209

Float

4

R

n/a

DECS Control

Control Output OEL

40211

Float

4

R

n/a

DECS Control

Control Output UEL

40213

Float

4

R

n/a

DECS Control

Control Output SCL

40215

Float

4

R

n/a

DECS Control

Control Output AVR

40217

Float

4

R

n/a

DECS Control

Control Output FCR

40219

Float

4

R

n/a

DECS Control

Control Output FVR

40221

Float

4

R

n/a

DECS Control

Invert Output (SCT/PPT)

40223

Uint

4

RW

Disabled=0 Enabled=1

Security

Table 25. Security Group Parameters

Group

Name

Register

Type

Bytes

R/W

Range

Security

Secure Login

40500

String

34

RW

0 – 34

Security

Logout

40517

String

5

RW

0 – 5

Security

Current Access

40520

Uint32

4

R

No Access=0,
Read Access=1
Control Access=2
Operator Access=3
Setting Access=4
Design Access=5
Administrator Access=6

Binary Points

Table 26. Binary Point Group Parameters

Group

Name

Register

Type

Bytes

R/W

Range

System Data

RF trig

40900 bit 0

Uint16

2

R

True=1 False=0

System Data

PU logic

40900 bit 1

Uint16

2

R

True=1 False=0

System Data

Trip logic

40900 bit 2

Uint16

2

R

True=1 False=0

System Data

Logic trig

40900 bit 3

Uint16

2

R

True=1 False=0

System Data

Breaker Status

40900 bit 4

Uint16

2

R

True=1 False=0

Alarms

Real Time Clock Alarm

40900 bit 5

Uint16

2

R

True=1 False=0

Alarms

Date Time Set Alarm

40900 bit 6

Uint16

2

R

True=1 False=0

Alarms

Firmware Change Alarm

40900 bit 7

Uint16

2

R

True=1 False=0

Alarms

Frequency out of range alarm

40900 bit 8

Uint16

2

R

True=1 False=0

Alarms

Ethernet link lost alarm

40900 bit 9

Uint16

2

R

True=1 False=0

Alarms

USB com alarm

40900 bit 10

Uint16

2

R

True=1 False=0

Alarms

IRIG sync lost alarm

40900 bit 11

Uint16

2

R

True=1 False=0

Alarms

Logic equal none alarm

40900 bit 12

Uint16

2

R

True=1 False=0

Alarms

No user setting alarm

40900 bit 13

Uint16

2

R

True=1 False=0

Alarms

NTP sync lost alarm

40900 bit 14

Uint16

2

R

True=1 False=0

Alarms

Microprocessor Reset Alarm

40900 bit 15

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 1

40901 bit 0

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 2

40901 bit 1

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 3

40901 bit 2

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 4

40901 bit 3

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 5

40901 bit 4

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 6

40901 bit 5

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 7

40901 bit 6

Uint16

2

R

True=1 False=0

Alarms

Programmable Alarm 8

40901 bit 7

Uint16

2

R

True=1 False=0