beautypg.com

Port access configuration, Login and access controls, Access timeout – Basler Electric DECS-250N User Manual

Page 197

background image

9440500990 Rev D

181

DECS-250N

Security

Port Access Configuration

Communication port access is configured in BESTCOMSPlus on the Port Access Setup tab (Figure 156)
of the Device Security Setup area. To configure communication port access, perform the following steps.

1.

In the BESTCOMSPlus settings explorer, select Port Access Setup. This selection is located
under General Settings, Device Security Setup. When prompted, enter a username of “A” and a
password of “A” and log on. This factory-default username and password allows administrator-
level access. It is highly recommended that this factory-default password be changed immediately
to prevent undesired access.

2.

Highlight the desired communication port in the port list

A

.

3.

Select the unsecured access level

B

for the port.

4.

Select the secured access level

C

for the port.

5.

Save the configuration by clicking the Save port button

D

.

6.

Open the Communication menu, and click Upload Security to Device.

7.

BESTCOMSPlus

®

notifies you when the security upload is successful.

Figure 156. Port Access Configuration Settings

A

Port List: Displays available communication ports and the corresponding access levels.

B

Unsecured Access Level: Select None, Read, Control, Operator, Settings, Design, or Admin.

C

Secured Access Level: Select None, Read, Control, Operator, Settings, Design, or Admin.

D

Save Port: Click button to save port access settings.

Login and Access Controls

BESTCOMSPlus Navigation Path: Settings Explorer, General Settings, Device Security Setup, Access
Control

Additional controls are available to limit login time and login attempts. These control settings are
illustrated in Figure 157.

Access Timeout

The access timeout setting

A

maintains security by automatically withdrawing password access if a user

neglects to log out. If no activity is seen for the duration of the access timeout setting, password access is
automatically withdrawn.