beautypg.com

Basler Electric DECS-250N User Manual

Page 284

background image

268

9440500990 Rev D

PROFIBUS Communication

DECS-250N

Instance Name

Inst. #

Type

RW

Key Name

Unit

Range

OEL Scaling

124

Float

R/W

Oel Scale Takeover

Signal3 GG

V

-10 - 10

OEL Scaling

124

Float

R/W

Oel Scale Takeover

Scale1 GG

%

0 - 200

OEL Scaling

124

Float

R/W

Oel Scale Takeover

Scale2 GG

%

0 - 200

OEL Scaling

124

Float

R/W

Oel Scale Takeover

Scale3 GG

%

0 - 200

SCL Scaling

125

UINT32 R/W

Scl Scale Enable GG

No

Unit

DISABLED=0

Auxiliary Input=1

AEM RTD 1=2

AEM RTD 2=3

AEM RTD 3=4

AEM RTD 4=5

AEM RTD 5=6

AEM RTD 6=7

AEM RTD 7=8

AEM RTD 8=9

SCL Scaling

126

Float

R/W

SclScaleSignal1 GG

V

-10 - 10

SCL Scaling

126

Float

R/W

SclScaleSignal2 GG

V

-10 - 10

SCL Scaling

126

Float

R/W

SclScaleSignal3 GG

V

-10 - 10

SCL Scaling

126

Float

R/W

SclScalePoint1 GG

%

0 - 200

SCL Scaling

126

Float

R/W

SclScalePoint2 GG

%

0 - 200

SCL Scaling

126

Float

R/W

SclScalePoint3 GG

%

0 - 200

Underfreq/Volts per hertz

127

UINT32 R/W

Sys Option Under Freq

Mode GG

No

Unit

UF Limiter=0 V2H Limiter=1

Underfreq/Volts per Hertz

128

Float

R/W

Sys Option Under Freq

Hz GG

Hz

40 - 75

Underfreq/Volts per Hertz

128

Float

R/W

Sys Option Under Freq

Slope GG

No

Unit

0 - 3

Underfreq/Volts per Hertz

128

Float

R/W

Sys Option Vol Per Hz

Slope Hi GG

No

Unit

0 - 3

Underfreq/Volts per Hertz

128

Float

R/W

Sys Option Vol Per Hz

Slope Lo GG

No

Unit

0 - 3

Underfreq/Volts per Hertz

128

Float

R/W

Sys Option Vol PerHz

Slope Time GG

Sec

0 - 10

PSS Configure

129

UINT32 R/W

Sys Option Pss

Power Level

Enable GG

No

Unit

DISABLED=0 ENABLED=1

PSS Configure

130

Float

R/W

Pss Pri Power Level

Percentage GG

No

Unit

0 - 1

PSS Configure

130

Float

R/W

Pss Pri Power Level

Hysteresis GG

No

Unit

0 - 1

PSS Control Primary

131

UINT32 R/W

Pss Enable GG

No

Unit

DISABLED=0 ENABLED=1

PSS Control Primary

131

UINT32 R/W

PssPriSwitch10 GG

No

Unit

DISABLED=0 ENABLED=1

PSS Control Primary

131

UINT32 R/W

PssPriSwitch11 GG

No

Unit

DISABLED=0 ENABLED=1

PSS Control Primary

131

UINT32 R/W

PssPriSwitch3 GG

No

Unit

Frequency=0 Der. Speed=1

This manual is related to the following products: