Basler Electric DECS-250N User Manual
Page 284
268
9440500990 Rev D
PROFIBUS Communication
DECS-250N
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
OEL Scaling
124
Float
R/W
Oel Scale Takeover
Signal3 GG
V
-10 - 10
OEL Scaling
124
Float
R/W
Oel Scale Takeover
Scale1 GG
%
0 - 200
OEL Scaling
124
Float
R/W
Oel Scale Takeover
Scale2 GG
%
0 - 200
OEL Scaling
124
Float
R/W
Oel Scale Takeover
Scale3 GG
%
0 - 200
SCL Scaling
125
UINT32 R/W
Scl Scale Enable GG
No
Unit
DISABLED=0
Auxiliary Input=1
AEM RTD 1=2
AEM RTD 2=3
AEM RTD 3=4
AEM RTD 4=5
AEM RTD 5=6
AEM RTD 6=7
AEM RTD 7=8
AEM RTD 8=9
SCL Scaling
126
Float
R/W
SclScaleSignal1 GG
V
-10 - 10
SCL Scaling
126
Float
R/W
SclScaleSignal2 GG
V
-10 - 10
SCL Scaling
126
Float
R/W
SclScaleSignal3 GG
V
-10 - 10
SCL Scaling
126
Float
R/W
SclScalePoint1 GG
%
0 - 200
SCL Scaling
126
Float
R/W
SclScalePoint2 GG
%
0 - 200
SCL Scaling
126
Float
R/W
SclScalePoint3 GG
%
0 - 200
Underfreq/Volts per hertz
127
UINT32 R/W
Sys Option Under Freq
Mode GG
No
Unit
UF Limiter=0 V2H Limiter=1
Underfreq/Volts per Hertz
128
Float
R/W
Sys Option Under Freq
Hz GG
Hz
40 - 75
Underfreq/Volts per Hertz
128
Float
R/W
Sys Option Under Freq
Slope GG
No
Unit
0 - 3
Underfreq/Volts per Hertz
128
Float
R/W
Sys Option Vol Per Hz
Slope Hi GG
No
Unit
0 - 3
Underfreq/Volts per Hertz
128
Float
R/W
Sys Option Vol Per Hz
Slope Lo GG
No
Unit
0 - 3
Underfreq/Volts per Hertz
128
Float
R/W
Sys Option Vol PerHz
Slope Time GG
Sec
0 - 10
PSS Configure
129
UINT32 R/W
Sys Option Pss
Power Level
Enable GG
No
Unit
DISABLED=0 ENABLED=1
PSS Configure
130
Float
R/W
Pss Pri Power Level
Percentage GG
No
Unit
0 - 1
PSS Configure
130
Float
R/W
Pss Pri Power Level
Hysteresis GG
No
Unit
0 - 1
PSS Control Primary
131
UINT32 R/W
Pss Enable GG
No
Unit
DISABLED=0 ENABLED=1
PSS Control Primary
131
UINT32 R/W
PssPriSwitch10 GG
No
Unit
DISABLED=0 ENABLED=1
PSS Control Primary
131
UINT32 R/W
PssPriSwitch11 GG
No
Unit
DISABLED=0 ENABLED=1
PSS Control Primary
131
UINT32 R/W
PssPriSwitch3 GG
No
Unit
Frequency=0 Der. Speed=1